Monthly flick test: what to check
- Test key turned: every lamp and sign lit on battery
- Key turned back, charging light on
- Exit signs lit and readable from the escape route
- No damage, unit secure, diffuser clean
- Nothing blocks the light or the sign
How often emergency lighting should be tested
BS 5266-1, the code of practice for emergency lighting of premises, sets two routine tests and a record:
- Monthly: a short functional test, the flick test. Simulate a mains failure with the test key and check every light and exit sign comes on from its battery.
- Annually: a test for the full rated duration of the system, usually 3 hours, to prove the batteries last as long as they have to.
- Every test, fault and repair written in the emergency lighting log book.
Why it is a legal duty
In England and Wales, article 17 of the Regulatory Reform (Fire Safety) Order 2005 makes the responsible person keep fire safety equipment, emergency lighting included, subject to a suitable system of maintenance and in efficient working order and good repair. BS 5266-1 is the standard fire risk assessors and fire and rescue services measure that against; the current edition is BS 5266-1:2025. Scotland and Northern Ireland have their own fire safety law with a similar maintenance duty.
How to test emergency lighting: the monthly flick test
Keep it short, just long enough to see every light. The long test is the annual one.
- Find the test key switch (often a fishtail key), usually near the distribution board or on each lighting circuit.
- Turn it to cut the supply to the emergency lights only, so they switch to battery.
- Walk the escape routes: every emergency light and exit sign should be lit.
- Turn the key back and check the charging indicators come on, usually a green light.
- Write each light's result in the log, and have any fault repaired.
The annual full-duration test
Once a year each light runs on battery for its full rated duration, usually 3 hours, and must stay lit to the end. It leaves the batteries flat, and they can take up to 24 hours to recharge, so run it at a quiet time, or test alternate lights so half the system stays charged. Most buildings have it done by an electrician or an emergency lighting contractor.
Who can test emergency lighting
A competent person. For the monthly flick test that can be a trained member of staff, a caretaker or the managing agent. The annual test and any repairs are usually done by an electrician or an emergency lighting contractor.
Self-test emergency lighting
Self-test luminaires run their own tests and show the result on an indicator. Someone still has to look at the indicators every month and record what they show.
Questions
How often should emergency lighting be tested?
Monthly with a short flick test, and once a year for the full rated duration, usually 3 hours, under BS 5266-1. Every test goes in the log book.
What is an emergency lighting flick test?
The monthly functional test: you turn the test key to simulate a mains failure, check that every emergency light and exit sign comes on from its battery, then turn it back.
How long is the monthly test?
Just long enough to see every light come on and stay on, usually a few minutes. The long test, for the full rated duration, is the annual one.
Who can test emergency lighting?
A competent person. Trained staff can do the monthly flick test; the annual test is usually left to an electrician or a contractor.
Do I need an emergency lighting log book?
Yes. BS 5266-1 asks for a record of every test, fault and repair, and your fire risk assessor or the fire and rescue service will ask to see it.
A plain-language summary, not a substitute for the law or the relevant British Standards. Your fire risk assessment and your local fire and rescue service have the final word.