InspectKeeper

Checklists /

Fire door checks

In blocks of flats over 11 metres high, regulation 10 puts the fire door checks on the responsible person: communal doors at least every 3 months, flat entrance doors at least once a year. In other buildings, as often as the fire risk assessment says. Here are the points, and a sheet to record them.

What to check on each door

  1. Door, frame and surrounding wall undamaged, no other damage
  2. Letterbox intact and closing (where fitted)
  3. Glazing intact, not cracked or loose
  4. Hinges, locks and ironmongery secure, nothing missing
  5. Gaps at the sides and top no more than 4 mm
  6. Intumescent strips and smoke seals undamaged (where fitted)
  7. Self-closer shuts the door fully into the frame
  8. No alterations: no new holes, cut-outs or removed parts
  9. Not wedged or propped open

Print this as a log sheet

Who has to check, and how often

Regulation 10 of the Fire Safety (England) Regulations 2022 has applied since 23 January 2023. In every building with two or more flats and common parts that residents would use to evacuate, the responsible person has to give residents information about fire doors. Where the top storey is more than 11 metres above the ground, the responsible person must also:

  • Check the fire doors in the common parts, self-closers included, at least every 3 months.
  • Use best endeavours to check every flat entrance door, self-closer included, at least every 12 months.
  • Keep a record of the steps taken to check the flat entrance doors, including visits where a resident refused access.

Who can do the checks

The government guidance says the checks should be simple and basic and should not need a specialist: caretakers, managing agents, housing officers and maintenance staff can do them with some instruction. They are visual and need no tools. Repairs are different: they go to a competent contractor as soon as reasonably practicable.

What to tell residents

Every resident must be told, as soon as reasonably practicable after moving in and again within each 12-month period, that fire doors should be kept shut when not in use, that self-closers must not be tampered with, and that any fault should be reported to the responsible person straight away.

A check is not a survey

Quarterly and yearly checks catch the everyday failures: a door wedged open, a closer that stops short, a damaged seal. They do not replace a periodic assessment of the doors by a fire safety specialist, which your fire risk assessment should plan for.

Outside England

Regulation 10 applies in England only. Wales is covered by the same Fire Safety Order but not by regulation 10; Scotland and Northern Ireland have their own fire safety law. The same checks are good practice there, on the schedule your fire risk assessment sets.

Questions

How often should fire doors be checked?

In blocks of flats over 11 metres in England: doors in the common parts at least every 3 months and flat entrance doors at least every 12 months, under regulation 10. In other buildings, as often as your fire risk assessment says; many check communal doors monthly or quarterly.

Does a fire door check need a qualified inspector?

No. The checks are visual, and the guidance expects caretakers, managing agents or maintenance staff to do them. A specialist is needed for repairs and for periodic fire door surveys.

What gap should there be around a fire door?

No more than 4 mm at the sides and top, per the gov.uk guidance; about 3 mm is typical. At the bottom, as small as practicable without the door catching on the floor. The door's manufacturer or certification may set tighter limits.

What if a resident will not let you check their flat door?

Record each attempt and the refusal, and try again. The duty for flat entrance doors is best endeavours, and the record is what shows you made them.

Do the checks have to be recorded?

For flat entrance doors, regulation 10 asks for a record of the steps taken. A dated log of every check, communal doors included, is the simplest way to show the fire and rescue service the checks were done.

A plain-language summary, not a substitute for the law or the relevant British Standards. Your fire risk assessment and your local fire and rescue service have the final word.