Under BS 5306-3 every fire extinguisher gets a visual check at least once a month, a basic service by a competent person every year and an extended service every 5 years (an overhaul every 10 for CO2). The monthly check takes under a minute per extinguisher and your own staff can do it. Here are the points, and a sheet to record them.

Fire extinguisher checklist: the monthly check

  1. In its designated place, visible and unobstructed
  2. Pressure gauge in the green zone (where fitted)
  3. Safety pin and tamper seal intact
  4. No visible damage, corrosion, leaks or blocked hose or horn
  5. Operating instructions legible and facing outward
  6. Service label present, basic service within the last 12 months

Print this as a log sheet

How often fire extinguishers should be checked

BS 5306-3, the code of practice for commissioning and maintaining portable fire extinguishers, sets a routine check and three levels of service:

  • Monthly, or more often where extinguishers can be knocked or tampered with: a visual check by the responsible person or someone they appoint.
  • Every 12 months: a basic service by a competent person, on every extinguisher.
  • Every 5 years: an extended service (a test discharge and refill) for water-based extinguishers, meaning water, foam and wet chemical, and for powder (10 years for sealed powder).
  • Every 10 years: an overhaul, including a pressure test of the cylinder, for CO2 and clean agent extinguishers.

Why it is a legal duty

In England and Wales, article 17 of the Regulatory Reform (Fire Safety) Order 2005 makes the responsible person keep fire safety equipment, extinguishers included, subject to a suitable system of maintenance and in efficient working order and good repair. Fire risk assessors, insurers and fire and rescue services judge that duty against BS 5306-3. Scotland and Northern Ireland have their own fire safety law with a similar maintenance duty.

Who can do the monthly check

Anyone the responsible person appoints and shows what to look for: a caretaker, a managing agent, a member of staff. Neither the Fire Safety Order nor BS 5306-3 asks for a qualification for it. The services are different: they need a competent person, usually an engineer from a company registered to BAFE SP101.

What to record

Write down every monthly check: the date, who did it, each extinguisher by its number or location, and any fault found, with what was done about it. Keep the engineer's certificates for the basic and extended services with the log. Your fire risk assessor, your insurer and the fire and rescue service will ask to see the record.

If something fails

A missing pin, a broken seal, a gauge out of the green, a dent or corrosion: take the extinguisher out of use, put a working one in its place if you can, and call your service company. A broken seal can mean the extinguisher has been used; an extinguisher that has been discharged, even partly, needs a recharge before it goes back on the wall.

The weekly fire alarm test (BS 5839-1)

If the building has a fire alarm system, BS 5839-1 asks for a test every week on top of the extinguisher checks. A member of staff the responsible person appoints can do it; no qualification is needed:

  • Operate one manual call point with the test key, a different one each week in rotation, so every call point gets tested over time.
  • Check the panel shows the right zone and the sounders can be heard, then reset the system.
  • Test at about the same time each week, so people in the building know it is a test.
  • Write the date, the call point and the result in the fire alarm log book.
  • Have the whole system serviced by a competent fire alarm engineer every 6 months.

Questions

How often should fire extinguishers be checked?

Visually at least once a month by the responsible person or someone they appoint, and serviced by a competent person every 12 months, under BS 5306-3. On top of that, an extended service every 5 years for water-based and powder extinguishers (10 years for sealed powder), and an overhaul every 10 years for CO2 and clean agent.

Who can check fire extinguishers?

Anyone the responsible person appoints can do the monthly visual check; no qualification is required. The annual basic service and the 5- and 10-year services need a competent person, usually a BAFE SP101-registered engineer.

What is the difference between a basic and an extended service?

The basic service is the yearly examination by an engineer. The extended service, every 5 years for most types (10 for sealed powder), adds a test discharge and refill to prove the extinguisher works. CO2 and clean agent extinguishers get an overhaul with a pressure test every 10 years instead.

Do fire extinguisher checks have to be recorded?

Yes. Keep a dated record of every monthly check and every service. It is how you show the fire and rescue service and your insurer that the extinguishers are maintained.

How often should a fire alarm be tested?

Weekly, under BS 5839-1: one manual call point each week, a different one each time, with the result in the log book. A competent engineer services the system every 6 months.

A plain-language summary, not a substitute for the law or the relevant British Standards. Your fire risk assessment and your local fire and rescue service have the final word.